Local Storage seems to be disabled in your browser.
For the best experience on our site, be sure to turn on Local Storage in your browser.
Schneider GZ1E14, Motor Circuit Breaker, Easy TeSys Power, GZ1E, AC-3, 3 Pole, 6~10A, Thermal Magnetic Trip
In stock
SKU
GZ1E14
Special Price
₹3,425.70
Regular Price
₹9,015.00
Schneider GZ1E14, Motor Circuit Breaker, Easy TeSys Power, GZ1E, AC-3, 3 Pole, 6~10A, Thermal Magnetic Trip is available to buy in increments of 1
Check Delivery Options at your Area


FREE SHIPPING
Free Shipping by Surface Only*


SECURE PAYMENT
100% Secure Payment
| Main | |
|---|---|
| Range | Easy TeSys |
| Range of product | Easy TeSys Power |
| Product or component type | Circuit breaker |
| Device short name | GZ1E |
| Device application | Motor |
| Trip unit technology | Thermal-magnetic |
| Suitability for isolation | Yes conforming to IEC 60947-1 appendix 7.1.6 |
| Colour | Grey (RAL 7011) |
| Complementary | |
| Poles description | 3P |
| Network type | AC |
| Utilisation category | AC-3 |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
| Mounting mode | By clips, By screws |
| Mounting support | Rail |
| Mounting position | Any position |
| Motor power kW |
2.2 kW at 230 V AC 50/60 Hz 4 kW at 400 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz 5.5 kW at 500 V AC 50/60 Hz 7.5 kW at 690 V AC 50/60 Hz |
| Breaking capacity |
Icu: ≥ 100 kA at 230/240 V AC 50/60 Hz Icu: ≥ 100 kA at 400/415 V AC 50/60 Hz Icu: 10 kA at 440 V AC 50/60 Hz Icu: 8 kA at 500 V AC 50/60 Hz Icu: 2 kA at 690 V AC 50/60 Hz |
| [Ics] rated service short-circuit breaking capacity |
100% at 230/240 V AC 50/60 Hz 100% at 400/415 V AC 50/60 Hz 100% at 440 V AC 50/60 Hz 100% at 500 V AC 50/60 Hz 75% at 690 V AC 50/60 Hz |
| Control type | Push-button |
| Thermal protection adjustment range | 6…10 A |
| Magnetic tripping current | 138 A |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Power dissipation | 2.5 W (per pole) |
| Mechanical durability | 100000 cycles |
| Electrical durability | 100000 cycles for AC-3 |
| Maximum operating rate | 25 cyc/h |
| Connections - terminals |
Screw clamp terminals 2 × 1…6 mm² (solid) Screw clamp terminals 2 × 1.5…6 mm² (flexible without end) Screw clamp terminals 2 × 1…4 mm² (flexible with end) |
| Height | 89 mm |
| Width | 44.5 mm |
| Depth | 78 mm |
No specifications available for this product.
Write Your Own Review