Schneider LRE365, Easy TeSys differential thermal overload relay 80...104 A - class 10A Schneider LRE365, Easy TeSys differential thermal overload relay 80...104 A - class 10A Schneider LRE365, Easy TeSys differential thermal overload relay 80...104 A - class 10A Schneider LRE365, Easy TeSys differential thermal overload relay 80...104 A - class 10A

Schneider LRE365, Easy TeSys differential thermal overload relay 80...104 A - class 10A

In stock
SKU
LRE365
Special Price ₹3,484.65 Regular Price ₹8,935.00
(18% GST Extra)
Add to Wish List
  • Differential thermal overload relay, thermal setting range 80–104A, tripping class 10A (IEC 60947‑4‑1 compliant); protects 3‑phase motors 45–55 kW @ 400V, suitable with fuses or GV2 L / GV3 L circuit breakers
  • Direct mounting on EasyPact TVS contactors, screw clamp terminal connection
  • Detects phase unbalance/overload, provides manual or automatic reset, trip auxiliary contact, and flag indicator
  • Conforms to IEC, UL, CSA, CCC, EAC, and Marine certifications
  • Green Premium compliant (RoHS/REACH) for global availability
Check Delivery Options at your Area

FREE SHIPPING

Free Shipping by Surface Only*

SECURE PAYMENT

100% Secure Payment

Main
Range Easy TeSys
Range of product Easy TeSys Protect
Product or component type Differential thermal overload relay
Device short name LRE
Relay application Motor protection
Phase failure sensitivity Tripping current 130% of Ir on two phase, the last one at 0 (IEC 60947-4-1)
Complementary
Product compatibility LC1E95
Network type AC
Network frequency 50…60 Hz
Mounting support Under contactor
Plate, with specific accessories
Rail, with specific accessories
Thermal overload class Class 10A conforming to IEC 60947-4-1
Signalling function Relay trip indicator
Thermal protection adjustment range 80…104 A
Tripping threshold 1.14 ± 0.06 Ir conforming to IEC 60947-4-1
Mechanical robustness Shocks: 6 Gn for 11 ms (IEC 60068-2-7)
Vibrations: 3 Gn (IEC 60068-2-6)
Auxiliary contact composition 1 NO + 1 NC
[Ith] conventional free air thermal current 5 A for signalling circuit
[Ue] rated operational voltage ≤ 690 V AC
Associated fuse rating 80 A aM for power circuit
160 A gG for power circuit
5 A gG for signalling circuit
[Ui] rated insulation voltage 690 V (IEC 60947-4-1)
[Uimp] rated impulse withstand voltage 6 kV
Local signalling Trip indicator
Control type Push-button red stop
Push-button green reset
Temperature compensation -20…60 °C
Connections - terminals (Signalling circuit) Screw clamp terminals, 2× 1…2.5 mm² flexible without cable end
Screw clamp terminals, 2× 1…2.5 mm² flexible with cable end
Screw clamp terminals, 2× 1…2.5 mm² solid without cable end
Connections - terminals (Power circuit) Screw clamp terminals, 1× 4…35 mm² flexible without cable end
Screw clamp terminals, 1× 4…35 mm² flexible with cable end
Screw clamp terminals, 1× 4…35 mm² solid without cable end
Recommended tightening torque Power circuit: 9 N·m
Signalling circuit: 1.7 N·m
Height 54 mm
Width 70 mm
Depth 113 mm