Schneider LRE365, Easy TeSys differential thermal overload relay 80...104 A - class 10A
Schneider LRE365, Easy TeSys differential thermal overload relay 80...104 A - class 10A Schneider LRE365, Easy TeSys differential thermal overload relay 80...104 A - class 10A Schneider LRE365, Easy TeSys differential thermal overload relay 80...104 A - class 10A Schneider LRE365, Easy TeSys differential thermal overload relay 80...104 A - class 10A

Schneider LRE365, Easy TeSys differential thermal overload relay 80...104 A - class 10A

In stock
SKU
LRE365
Special Price ₹3,484.65 Regular Price ₹8,935.00
(18% GST Extra)
Add to Wish List
  • Differential thermal overload relay, thermal setting range 80–104A, tripping class 10A (IEC 60947‑4‑1 compliant); protects 3‑phase motors 45–55 kW @ 400V, suitable with fuses or GV2 L / GV3 L circuit breakers
  • Direct mounting on EasyPact TVS contactors, screw clamp terminal connection
  • Detects phase unbalance/overload, provides manual or automatic reset, trip auxiliary contact, and flag indicator
  • Conforms to IEC, UL, CSA, CCC, EAC, and Marine certifications
  • Green Premium compliant (RoHS/REACH) for global availability
Check Delivery Options at your Area

FREE SHIPPING

Free Shipping by Surface Only*

SECURE PAYMENT

100% Secure Payment

Main
RangeEasy TeSys
Range of productEasy TeSys Protect
Product or component typeDifferential thermal overload relay
Device short nameLRE
Relay applicationMotor protection
Phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0 conforming to IEC 60947-4-1
Complementary
Product compatibilityLC1E95
Network typeAC
Network frequency50...60 Hz
Mounting support Under contactor
Plate, with specific accessories
Rail, with specific accessories
Thermal overload classClass 10A conforming to IEC 60947-4-1
Signalling functionRelay trip indicator
Thermal protection adjustment range80…104 A
Tripping threshold1.14 ± 0.06 Ir conforming to IEC 60947-4-1
Mechanical robustness Shocks: 6 Gn for 11 ms conforming to IEC 60068-2-7
Vibrations: 3 GN conforming to IEC 60068-2-6
Auxiliary contact composition1 NO + 1 NC
[Ith] conventional free air thermal current5 A for signalling circuit
[Ue] rated operational voltage<= 690 V AC
Associated fuse rating 80 A aM for power circuit
160 A gG for power circuit
5 A gG for signalling circuit
[Ui] rated insulation voltage690 V conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage6 kV
Local signallingTrip indicator
Control type Push-button red stop:
Push-button green reset:
Temperature compensation-20…60 °C
Connections – terminals Signalling circuit: screw clamp terminals 2 1…2.5 mm² flexible without cable end
Signalling circuit: screw clamp terminals 2 1…2.5 mm² flexible with cable end
Signalling circuit: screw clamp terminals 2 1…2.5 mm² solid without cable end
Power circuit: screw clamp terminals 1 4…35 mm² flexible without cable end
Power circuit: screw clamp terminals 1 4…35 mm² flexible with cable end
Power circuit: screw clamp terminals 1 4…35 mm² solid without cable end
Recommended tightening torque Power circuit: 9 N.m – on screw clamp terminals
Signalling circuit: 1.7 N.m – on screw clamp terminals
Height54 mm
Width70 mm