Schneider LV525312, MCCB, EasyPact CVS250B, 25 kA at 415 VAC, 200 A rating thermal magnetic TM-D trip unit, 4 Pole Schneider LV525312, MCCB, EasyPact CVS250B, 25 kA at 415 VAC, 200 A rating thermal magnetic TM-D trip unit, 4 Pole Schneider LV525312, MCCB, EasyPact CVS250B, 25 kA at 415 VAC, 200 A rating thermal magnetic TM-D trip unit, 4 Pole Schneider LV525312, MCCB, EasyPact CVS250B, 25 kA at 415 VAC, 200 A rating thermal magnetic TM-D trip unit, 4 Pole

Schneider LV525312, MCCB, EasyPact CVS250B, 25 kA at 415 VAC, 200 A rating thermal magnetic TM-D trip unit, 4 Pole

In stock
SKU
LV525312
Special Price ₹11,680.00 Regular Price ₹29,200.00
(18% GST Extra)
Add to Wish List
  • 4 poles 3d fixed circuit breaker with high performance and cost-saving functionality for small and medium-sized buildings.
  • Breaking capacity: 25kA rms at 415VAC 50/60Hz; Operational voltage: 440VAC 50/60Hz.
  • 200A thermal-magnetic trip unit (TMD) with adjustable thermal overload and fixed magnetic protection.
  • Dimensions: 140mm x 161mm x 86mm, with optional functions and accessories available.
  • Complies with IEC 60947, CCC, EAC standards; suitable for class II insulation switchboards (IEC 60664-1).
Check Delivery Options at your Area

FREE SHIPPING

Free Shipping by Surface Only*

SECURE PAYMENT

100% Secure Payment

EasyPact CVS250B Specifications
Main
RangeEasyPact
Range of productEasyPact CVS100...250
Product nameEasyPact CVS
Device short nameCVS250B
Product or component typeCircuit breaker
Device applicationDistribution
Poles description4P
Protected poles description3D
Earth leakage protectionWithout
Rated current [In]200 A at 40 °C
Network typeAC
Utilisation categoryCategory A
Breaking capacity [Icu] 40 kA at 220/240 V AC
25 kA at 380/415 V AC
20 kA at 440 V AC
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Trip unit rating200 A at 40 °C
Protection typeShort-circuit (magnetic), Overload (thermal)
Complementary
Rated impulse withstand voltage [Uimp]8 kV
Network frequency50/60 Hz
Breaking capacity codeB
Rated service breaking capacity [Ics] 15 kA at 440 V AC
25 kA at 380/415 V AC
40 kA at 220/240 V AC
Neutral positionLeft
Mechanical durability20000 cycles
Electrical durability10000 cycles at 415 V In
Control typeToggle
Thermal protection adjustment range140…200 A
Neutral protection settingNo protection (3D)
Mounting modeFixed
ConnectionsScrew connection
Dimensions (W x D x H)140 x 86 x 161 mm